From the makers’ manuals and the code
Does a sauna need a dedicated circuit?
Yes. Electric heaters get their own 240 V circuit, installed by a licensed electrician, and no receptacles are allowed inside the hot room [Harvia Spirit manual]. Plug-in infrared saunas often still need a dedicated 120 V circuit: Sunlighten’s mPulse Aspire calls for a dedicated 20 A circuit and a NEMA 5-20 outlet, with no extension cords [Sunlighten mPulse Aspire spec sheet]. Clearlight’s larger cabins run on 240 V, 15–20 A [Clearlight electrical requirements].
How many amps does a sauna heater draw?
About 4.17 A per kW at 240 V (amps = watts ÷ volts). 4.5 kW ≈ 18.75 A, 6 kW = 25 A, 8 kW ≈ 33.3 A, 9 kW = 37.5 A.
What does the 125% rule mean for a sauna breaker?
The National Electrical Code treats fixed space heating as a continuous load (424.3(B)), so wire and breaker must carry 125% of the heater’s current (210.19(A)(1), 210.20(A)) [NEC continuous-load sizing (EC&M)]. Some manuals specify less: HUUM lists a 30 A breaker for its 25 A Drop 6, while 125% of 25 A is 31.25 A. When they differ, your electrician or inspector decides.
Do outdoor saunas need a GFCI?
Possibly. Recent electrical codes widen GFCI protection outdoors; the 2026 NEC reportedly covers circuits up to 60 A, including accessory buildings [Mike Holt forum: outdoor sauna on GFCI (secondary)]. Finnleo, HUUM and Saunum advise against GFCIs on their heaters because they nuisance-trip [Finnleo Himalaya manual]. The inspector decides.
What wire should a sauna heater use?
Copper rated at least 90 °C (194 °F) [Harvia Spirit manual]. Manuals list 10 AWG for most 4.5–6 kW heaters and 8 AWG (Finnleo: #6 for 9 kW) for bigger ones. See the table.